Operator’s
Manual
Seri es 300
Automatic Transfer Switches
G des ig n, 1000 thro ug h 3000 amp. size s
TABLE OF CONTENTS
section
INSTALLATION 1..........................
SEQUENCE OF OPERA TION 2.............
TESTING & SERVICE 3....................
ADJUSTMENTS 4.........................
CONTROL FEATURES 5...................
INDEX back cover.........................
An experienced licensed electrician must install theATS.
1000, 1200, 1600 amp. sizes
DANGER is used in this manual to warn of high
voltages capable of causin g shock , burn s, or death.
WARNINGisusedinthismanualtowarn
of possible perso nal injury.
!
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
!
Refer to the outline and wiring drawings provided
with ASCO Series 300 ATS for all installation details.
2000 amp. size
Vue de la page 0
1 2 3 4 5 6 ... 18 19

Résumé du contenu

Page 1 - Operator’s

381333–122 D50 Hanover Road, Florham Park, New Jersey 07932–1591 USAFor sales or service call 1 800 800–2726 (ASCO) www .ascopower.comIn Canada: PO Bo

Page 2

TESTING & SERVICE(continued)3-- 2MANUAL LOAD TRANSFERThis procedure will manually transfer the load if thecontroller is disconnected.Do not manual

Page 3 - SECTION 1 INSTALLATION

SECTION 4 ADJUSTMENTS4-- 1Time Delay AdjustmentStandard time delays are set to customer specifications(if none specified, standard factory settings ar

Page 4 - INSTALLATION (continued)

ADJUSTMENTS(continued)4-- 2Do not make any setting changeswhile the controller is energized.!How to Change a Setting1. Prevent the transfer switch fro

Page 5 - Functional Test

SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS5-- 1These timers periodically exercise the emergency engine-generator plant. They can be set to exercis

Page 6

CONTROL FEATURES (continued)5-- 2Optional Accessory 11BG – SOURCE AVAILABILITY SIGNAL& PROGRAMMABLE ENGINE EXERCISER MODULE2–linedisplay3 buttonsc

Page 7

CONTROL FEATURES (continued)5-- 3How to Set Optional Programmable Engine Exerciser (part of Acc. 11BG module)Hazardous voltage capable of causing shoc

Page 8 - Retransfer to Normal

CONTROL FEATURES (continued)5-- 4Programmable Engine Exerciser SettingsFill in your settings for future referenceWeekly or Bi–weekly Day of Week Start

Page 9 - DISCONNECTING THE CONTROLLER

CONTROL FEATURES (continued)5-- 5INPHASE MONITORFOR MOTOR LOAD TRANSFERInphase monitoring logic controls transfer and retransferof motor loads, so tha

Page 10 - TESTING & SERVICE

CONTROL FEATURES (continued)5-- 6OPTIONAL STRIP HEATER (Accessory 44)Accessory 44 Strip Heater is designed to keep ambienttemperatures within the Auto

Page 11 - SECTION 4 ADJUSTMENTS

INDEXPrinted in U.S.A.E 2005 ASCO Power Technologies, L.P.Aaccessories, 5–2, 5–3, 5–4, 5–5auxiliary circuits, 1–2Bbarriers, 1–3battery, 4–2, 5–1button

Page 12 - ADJUSTMENTS

Namepl ateThe Transfer Switch nameplate includes data for eachspecific ASCO Series 300 ATS. Use the ATS onlywithin the limits shown on this nameplate.

Page 13 - Press until light FLASHES

SECTION 1 INSTALLATION1-- 1A S CO Series 300 Autom atic Transfer Switch es (ATSs) areListed under Underwriters Laboratories UL 1008 Standardfor Safety

Page 14

INSTALLATION (continued)1-- 2Controller GroundA grounding wire must be connected to the controller’slower left mounting stud. Because the controller i

Page 15 - CONTROL FEATURES (continued)

INSTALLATION (continued)1-- 3Functional TestThe Functional Test consists of three checks: manualoperation, voltage checks, and electrical operation.Do

Page 16

INSTALLATION (continued)1-- 4Press until light FLASHESPress for 15 SecondsFlorham Pa rk N J 07932 USATRANSFER SWITCH TEST BYPASS TIME DELAY SET ENGINE

Page 17 - REMOTE CONTROL FEATURES

INSTALLATION (continued)1-- 5Press until light FLASHESPress for 15 SecondsFlorham Pa rk N J 07932 USATRANSFER SWITCH TEST BYPASS TIME DELAY SET ENGINE

Page 18 - AVAILABLE KITS FROM ASCO

Hold 15 sec.tostart the enginegenerator and totransfer the loadto emergency.Press to cancel theactive exercise period(stops engine now orafter cooldow

Page 19 - Printed in U.S.A

SECTION 3 TESTING & SERVICE3-- 1PREVENTIVE MAINTENANCEReasonable care in preventive maintenance will insurehigh reliability and long life for the